Product Overview
This product is a PVC insulated flexible cable with a rated voltage of 450/750V and below, available in ordinary type and flame-retardant type, suitable for connecting relevant electrical equipment.
Executive Standard
GB/T 5023.3-2008
Cable Models
- 60227 IEC 02(RV)
- 60227 IEC 06(RV)
- Z (A, B, C)-60227 IEC 02 (RV) Note: Specific models and specification ranges are subject to the certificate.
Structural Parameter Table (I)
| Specification (mm²) | Conductor Structure (Strands / Single Wire Diameter mm) | Nominal Insulation Thickness (mm) | Approximate Outer Diameter (mm) | Approximate Weight (kg/km) | Minimum Insulation Resistance at 70℃ (MΩ·km) | Maximum Conductor Resistance at 20℃ (Ω/km) |
| 1.5 | 45/0.196 | 0.7 | 3.1 | 21 | 0.010 | 13.3 |
| 2.5 | 74/0.196 | 0.8 | 3.7 | 33 | 0.009 | 7.98 |
| 4 | 56/0.284 | 0.8 | 4.3 | 49 | 0.007 | 4.95 |
| 4 | 84/0.284 | - | 4.9 | - | 0.006 | 3.30 |
Structural Parameter Table (II)
| Specification (mm²) | Conductor Structure (Strands / Single Wire Diameter mm) | Nominal Insulation Thickness (mm) | Approximate Outer Diameter (mm) | Approximate Weight (kg/km) | Minimum Insulation Resistance at 70℃ (MΩ·km) | Maximum Conductor Resistance at 20℃ (Ω/km) |
| 0.5 | 16/0.192 | 0.6 | 2.2 | 9 | 0.013 | 39.0 |
| 0.75 | 24/0.192 | 0.6 | 2.4 | 12 | 0.011 | 26.0 |
Current-Carrying Capacity (In Air)
Basic Conditions
- Operating temperature: 70℃
- Ambient temperature: 40℃
Remarks
- Cables are in contact with each other;
- The center-to-center spacing of cables is 2 times the cable outer diameter when arranged in a plane.
Existing Parameters
| Conductor Operating Temperature (℃) | Ambient Temperature (℃) (In Air) | - | - | - | - | - | - | - |
| 70 | 1.36 | 1.28 | 1.19 | | | | | |