Rated voltage 450/750V and below cross-linked polyolefin insulated wires and cables
No.038
Description
English Version of Cable Parameters
Part 1: Cross-linked Polyolefin Insulated Wires and Cables with Rated Voltage up to and including 450/750V
1. Basic Product Information
- Product Name: Cross-linked Polyolefin Insulated Wires and Cables with Rated Voltage up to and including 450/750V
- Executive Standards: JB/T 10491-2022, GB/T 19666-2019
- Cable Model: WDZ(A/B/C)-RYJ-105
- Rated Voltage (U₀/U): 300/500V or 450/750V
- Manufacturer Address: No. 238 Zhenkang Road, Zhangyan Town, Jinshan District, Shanghai, P.R.China
2. Operating Environment & Installation Requirements
- Cable Laying Temperature: Not lower than the specified temperature (preheating of the cable is required)
- Minimum Bending Radius: 6D (D = cable outer diameter)
- Conductor Operating Temperature: Max. 105℃
- Ambient Temperature for Current-Carrying Capacity Reference: 40℃
3. Cable Structural Parameters
| Specification (mm²) |
Conductor Structure (No. of Wires / Single Wire Diameter, mm) |
Nominal Insulation Thickness (mm) |
Approximate Cable Outer Diameter (mm) |
Approximate Cable Weight (kg/km) |
Minimum Insulation Resistance at 105℃ (MΩ·km) |
Maximum Conductor Resistance at 20℃ (Ω/km) |
| 1×0.5 |
16/0.192 |
0.6 |
2.2 |
9 |
0.013 |
39.0 |
| 1×0.75 |
24/0.192 |
0.6 |
2.4 |
12 |
0.012 |
26.0 |
| 1×1 |
32/0.192 |
0.6 |
2.6 |
14 |
0.010 |
19.5 |
| 1×240 |
1759/0.40 |
2.2 |
24.8 |
2254 |
0.0028 |
- |
4. Current-Carrying Capacity (In Air)
- Model: WDZ(A/B/C)-RYJ-105
- Voltage: 300/500V or 450/750V
- Number of Cores: Single-core
- Arrangement: -
- Cross-Section & Current-Carrying Capacity (A): -
Notes:
- Cables are in contact with each other;
- For flat arrangement, the center-to-center spacing of cables is 2 times the cable outer diameter.
Part 2: RVV Cable Parameters
1. Product Overview
- Rated Voltage: 300/300V, 300/500V
- Insulation Material: Polyvinyl Chloride (PVC)
- Sheath Material: Polyvinyl Chloride (PVC)
- Flame Retardant Grade: Non-flame retardant, Grade ZA, Grade ZB, Grade ZC (Optional)
- Core Color:
- 2-core: Brown, Blue
- 3-core: Brown, Blue, Yellow/Green
- 5-core: Brown, Grey, Yellow/Green
- 6-core and above: White core + Black coding
- Sheath Color: Black (Default)
2. Executive Standards
- GB/T 5023.5-2008
- JB/T 8734.3-2016
- GB/T 19666-2019
3. Cable Models
- 60227 IEC 52(RVV)-300/300V
- 60227 IEC 53(RVV)-300/500V
- (ZA/ZB/ZC)-60227 IEC 52(RVV)-300/300V
4. Cable Structural Parameters
| Specification (mm²) |
Conductor Structure (No. of Wires / mm) |
Conductor Diameter (mm) |
Approximate Cable Outer Diameter (mm) |
Approximate Cable Weight (kg/km) |
|
|
|
|
|
|
|
|
|
Non-FR |
ZA |
ZB |
ZC |
Non-FR |
ZA |
ZB |
ZC |
| 2×0.5 |
16/0.192 |
0.90 |
5.3 |
5.4 |
5.4 |
5.3 |
32 |
35 |
35 |
32 |
| 2×0.75 |
24/0.192 |
1.10 |
6.1 |
6.2 |
6.2 |
6.1 |
43 |
47 |
47 |
43 |
| 2×4 |
56/0.284 |
2.50 |
10.8 |
10.9 |
10.9 |
10.8 |
154 |
163 |
163 |
154 |
| 2×6 |
84/0.284 |
3.00 |
11.8 |
11.9 |
11.9 |
11.8 |
199 |
210 |
210 |
200 |
| 2×10 |
74/0.4 |
4.00 |
15.0 |
15.3 |
15.3 |
15.0 |
325 |
348 |
348 |
326 |
| 3×4 |
56/0.284 |
2.50 |
11.7 |
11.8 |
11.8 |
11.7 |
206 |
215 |
215 |
206 |
| 3×6 |
84/0.284 |
3.00 |
12.7 |
12.9 |
12.9 |
12.7 |
270 |
280 |
280 |
270 |
| 3×10 |
74/0.4 |
4.00 |
16.4 |
16.7 |
16.7 |
16.4 |
451 |
475 |
475 |
452 |
| 4×4 |
56/0.284 |
2.50 |
12.8 |
12.9 |
12.9 |
12.8 |
259 |
268 |
268 |
259 |
| 4×6 |
84/0.284 |
3.00 |
14.0 |
14.1 |
14.1 |
14.0 |
342 |
353 |
353 |
342 |
| 4×10 |
74/0.4 |
4.00 |
18.0 |
18.3 |
18.3 |
18.0 |
574 |
600 |
600 |
575 |
| 4×2.5 |
74/0.196 |
2.00 |
11.3 |
11.5 |
11.5 |
11.3 |
188 |
196 |
196 |
188 |
| 5×0.75 |
24/0.192 |
1.10 |
8.4 |
8.5 |
8.5 |
8.4 |
94 |
99 |
99 |
94 |
| 5×1 |
32/0.192 |
1.28 |
8.9 |
9.0 |
9.0 |
8.9 |
111 |
116 |
116 |
111 |
| 5×1.5 |
45/0.196 |
1.52 |
10.5 |
10.6 |
10.6 |
10.5 |
155 |
162 |
162 |
155 |
| 5×4 |
56/0.284 |
2.50 |
14.3 |
14.5 |
14.5 |
14.3 |
327 |
339 |
339 |
327 |
| 5×6 |
84/0.284 |
3.00 |
15.7 |
15.8 |
15.8 |
15.7 |
431 |
444 |
444 |
431 |
| 5×10 |
74/0.196 |
2.00 |
12.6 |
12.7 |
12.7 |
12.6 |
233 |
242 |
242 |
233 |
| 12×1 |
32/0.192 |
1.28 |
13.2 |
13.3 |
13.3 |
13.2 |
252 |
262 |
262 |
252 |
| 15×0.75 |
24/0.192 |
1.10 |
11.8 |
11.9 |
11.9 |
11.8 |
212 |
221 |
221 |
212 |
| 15×1 |
32/0.192 |
1.28 |
14.6 |
14.7 |
14.7 |
14.6 |
307 |
319 |
319 |
307 |
| 16×0.75 |
24/0.192 |
1.10 |
11.8 |
11.9 |
11.9 |
11.8 |
221 |
228 |
228 |
221 |
| 20×0.75 |
24/0.192 |
1.10 |
15.2 |
15.3 |
15.3 |
15.2 |
328 |
340 |
340 |
328 |
| 20×1 |
32/0.192 |
1.28 |
16.2 |
16.3 |
16.3 |
16.2 |
390 |
404 |
404 |
390 |
| 24×1 |
32/0.192 |
1.28 |
17.9 |
18.0 |
18.0 |
17.9 |
466 |
483 |
483 |
466 |
| 25×0.75 |
24/0.192 |
1.10 |
16.8 |
16.9 |
16.9 |
16.8 |
400 |
415 |
415 |
400 |
| 25×1 |
32/0.192 |
1.28 |
17.9 |
18.0 |
18.0 |
17.9 |
477 |
494 |
494 |
478 |
| 30×0.75 |
24/0.192 |
1.10 |
18.2 |
18.3 |
18.3 |
18.2 |
480 |
496 |
496 |
480 |
| 30×1 |
32/0.192 |
1.28 |
19.3 |
19.5 |
19.5 |
19.3 |
573 |
591 |
591 |
573 |
| 37×0.75 |
24/0.192 |
1.10 |
19.6 |
19.7 |
19.7 |
18.7 |
547 |
556 |
556 |
596 |
| 37×1 |
32/0.192 |
1.28 |
20.8 |
21.0 |
21.0 |
27.5 |
657 |
666 |
666 |
687 |
| 40×0.75 |
24/0.192 |
1.10 |
20.4 |
20.5 |
20.5 |
20.4 |
615 |
634 |
634 |
616 |
| 40×1 |
32/0.192 |
1.28 |
21.7 |
21.8 |
21.8 |
21.7 |
737 |
759 |
759 |
738 |
| 41×0.75 |
24/0.192 |
1.10 |
21.2 |
21.3 |
21.3 |
21.2 |
640 |
663 |
663 |
641 |
| 41×1 |
32/0.192 |
1.28 |
22.5 |
22.7 |
22.7 |
22.5 |
767 |
792 |
792 |
768 |
5. Correction Factors for Current-Carrying Capacity at Different Ambient Temperatures
| Conductor Operating Temperature (℃) |
Correction Factors Corresponding to Ambient Temperature (℃, In Air) |
|
|
|
|
|
|
|
|
20 |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
| 70 |
1.36 |
1.28 |
1.19 |
1.10 |
1.00 |
0.90 |
0.78 |
- |
Notes on Abbreviations
- FR: Flame Retardant
- Max.: Maximum
- Min.: Minimum
- Approx.: Approximate